Who should perform the final door assembly inspection?
The final inspection should be performed by the general contractor's quality team or a qualified door hardware consultant. For fire-rated assemblies, NFPA 80 requires that inspections be performed by individuals with knowledge of the operating components of the door assembly being inspected.
What if a fire label is damaged during installation?
If a fire label is damaged or removed during installation, the component must be relabeled by a qualified field inspection service (such as Intertek or UL) or replaced. Do not install fire-rated components with missing or illegible labels.
How do I document the final inspection?
Create an inspection report for each opening that includes: opening number and location, all component information, clearance measurements, functional test results (pass/fail), fire label photographs, and the inspector's signature and date. Retain this documentation for the building owner.
What is the most commonly failed item in a door assembly inspection?
Closer adjustment is the most commonly failed item. Doors that do not latch consistently, slam closed, or close too slowly all indicate closer adjustment issues. Test the closer by closing the door 10 consecutive times — it must latch every time without slamming.
Can a door assembly pass inspection with cosmetic damage?
Minor cosmetic damage (small scratches not visible at 3 feet, slight color variation) is typically acceptable. Dents, significant scratches, rust, or finish failure that affects corrosion protection should be repaired or the component replaced. The project specification may have specific finish acceptance criteria.