What happens if a fire label is missing or illegible?
A missing or illegible fire label means the component cannot be verified as fire-rated. Under NFPA 80, the component must be replaced or a qualified field inspection service must relabel it. Do not install components with missing labels in fire-rated openings.
Can I add a viewer or mail slot to a fire-rated door?
Only if the modification is covered under the door's listing. Most fire-rated doors have maximum glazing size limits and specific hardware prep allowances. Adding a viewer or any cutout not covered by the listing voids the fire rating. Consult the door manufacturer's listing for allowed modifications.
Are all five fire rating levels used in commercial construction?
Yes. The 20-minute, 45-minute, 60-minute, 90-minute, and 180-minute ratings are specified based on the wall rating and occupancy type. A 1-hour rated wall typically requires a 45-minute or 60-minute door. A 2-hour rated wall requires a 90-minute door. The 180-minute rating is used in vault and high-hazard applications.
How often must fire doors be inspected after installation?
NFPA 80 requires annual inspection and functional testing of all fire door assemblies. The inspection must verify self-closing, positive latching, clearances, label condition, and absence of unauthorized modifications.
Can I use non-fire-rated hinges on a fire-rated door?
No. All hardware on a fire-rated assembly must be fire-listed for the assembly rating. Standard commercial steel hinges are generally fire-listed, but decorative or specialty hinges may not be. Always verify the fire listing of every hardware component.