What is the minimum egress door width required by the IBC?
The IBC requires a minimum clear opening width of 32 inches for egress doors, measured between the face of the door and the stop with the door open 90 degrees (IBC 1010.1.1). A 36-inch nominal door is standard in commercial construction because it provides approximately 33-3/4 inches of clear width after accounting for hardware projection, satisfying both the 32-inch IBC minimum and accessibility requirements.
When does the IBC require doors to swing in the direction of egress?
Doors must swing in the direction of egress travel when the occupant load served by the door exceeds 50 (IBC 1010.1.2.1). This applies to each individual door along the egress path. High Hazard (Group H) occupancies require doors to swing in the direction of egress regardless of occupant load.
What fire rating does a door need in a 1-hour corridor wall?
A door in a 1-hour fire-rated corridor wall (fire partition) requires a minimum 20-minute fire protection rating (IBC Table 716.1). The door must be self-closing, self-latching, and the entire assembly (door, frame, hardware, and any glazing) must be listed and labeled for the 20-minute rating.
What is the difference between panic hardware and fire exit hardware?
Panic hardware is a door-latching device that releases when a horizontal force is applied to a push bar or crossbar. Fire exit hardware is panic hardware that has been tested and listed for use on fire-rated door assemblies. Standard panic hardware is not listed for fire-rated doors. When a fire-rated door requires panic hardware (such as an exit stairway door in an Assembly occupancy), fire exit hardware must be used.
Is glazing permitted in 90-minute fire-rated doors?
Yes, but glazing in 90-minute fire-rated doors is limited to a maximum of 100 square inches per lite, with a maximum dimension of 33 inches. The glazing must be fire-protection-rated and listed for the assembly. No glazing is permitted in 3-hour (180-minute) fire-rated doors.
Does NFPA 80 require annual fire door inspections?
Yes. NFPA 80 (2019 edition, Chapter 5) requires all fire door assemblies to be inspected annually by a knowledgeable individual. The inspection must verify that the door, frame, hardware, and glazing are intact, that clearances do not exceed maximums (1/8 inch at head and jambs, 3/4 inch at the bottom), that self-closing and self-latching devices function correctly, and that no field modifications have been made to the labeled assembly.
What are the maximum clearances for fire-rated door assemblies?
Per NFPA 80, the maximum clearance is 1/8 inch between the door and the frame at the head and jambs, and 1/8 inch at the meeting edges of paired doors. The maximum undercut (clearance at the bottom of the door) is 3/4 inch. Clearances exceeding these maximums compromise the fire rating of the assembly and must be corrected.
Can a fire-rated door be field-modified after installation?
NFPA 80 prohibits field modifications to labeled fire door assemblies unless the modification is specifically addressed by the product listing. Cutting, planing, adding non-listed hardware, or removing components from a labeled fire door voids the fire rating. Any necessary modifications must be performed in accordance with the manufacturer’s listing and approved by the AHJ.